Page 168 Chapter 10: Troubleshooting
002 - Station Flow Too High
Figure 143: Warning 002-Flow Upper Limit
This warning appears at any controller whenever the measured
flow is more than the expected flow (upper limit failure). The
warning displays the station number (2) which was on at the time
of the upper limit violation, the Master Valve (MV1) and/or
Pump, as well as the GPM reading (90) as measured by the flow
meter. Upon detection of this condition, the controller
automatically terminates irrigation on the station and advances to
the next station in the program. Condemned stations will not
irrigate again until the warning has been cleared.
Action:
Step 1 Check for:
a. Stuck valve (from previous station)
b. Broken pipes/heads
c. Incorrectly established individual station limits
d. Large variations in system water pressure
Step 2 If station limits are suspected, manually turn each
station on and observe the nominal GPM readings.
To manually turn on a station and read the flow,
refer to the Manual Test procedure, (8-2)
Step 3 Compare the GPM reading with the limit setting to
insure that adequate margin exits (typical: 20% over
nominal)
WARNING = FLOW UP LIMIT 06/20/96 10:45AM
STA=2, MV1 GPM=90 |¾||½|