Page 174 Chapter 10: Troubleshooting
005 - Station Electrical Current Too Low
Figure 146: Warning 005-Current Low Limit
The measured current lower limit value of electrical current is
less than the established limits. The warning lists the station
number (5) which was on at the time of the lower limit violation,
the Master Valve and/or Pump, as well as the measured electrical
current in amps (0.00). The current reading is the total or sum of
all outputs which are on. Upon detection of this condition, the
controller automatically terminates irrigation on the station and
advances to the next station in the program. Condemned stations
will not irrigate again until the warning has been cleared.
Action:
Step 1 Check field wiring for:
a. Faulty solenoid (open coil)
b. No station connection at terminal output board
c. Improper field wire connections at valve solenoid
d. Poor common connection in field wiring
e. Improper station limits
Step 2 If station limits are suspected, manually turn each
station on and observe the measured amperage
(electrical current) in the display area I=X.XX.
(Refer to Multi-Station Diagnostics procedure.)
Step 3 Compare the amperage reading with the limit setting
to insure that adequate margin exists (typical: 50%
under nominal).
WARNING = I LOW LIMIT 06/20/96 03:15PM
STA=5 I=0.00 |¾||½|