026 - FM - Multiple Normally Open Master Valves
Figure 167: Warning 026 -FM Multiple N.O. Assignment
This warning appears at the submaster whenever the Flow Max
feature has been incorrectly set up by the user. Using Flow Max,
it is possible to assign a device (in this case the Normally Open
Master Valve) to any of the Flow Max participants. If the user
makes an error by assigning the N.O. MV to more than one
satellite, this warning will appear at the submaster. Devices
must be installed at one physical location (satellite) only.
Action:
Step 1 Review the Flow Max device connection list at the
submaster via the F4=REVIEW ALL selection.
Look for two or more occurrences of the N.O. MV
throughout the Flow Max participants.
Step 2 Note the incorrect assignment and remove it from
the location(s) which are in error.
Example:
Assume a N.O. MV physical connection is at
submaster (address 01-00) and the N.O. MV was
inadvertent assigned to participant address 01-
03.
To remove the incorrect assignment go to the
satellite address 01-03 (fourth controller on the
hardwire link) and delete the entry using the
Flow Max setup function.
WARNING = MULTIPLE N.O. 06/03/96 06:45PM