Page 166 Chapter 10: Troubleshooting
Standard Flow Warnings
001 - Station Flow Too Low
Figure 142: Warning 001 -Flow Lower Limit
This warning appears at any controller whenever the measured
flow is less than the expected flow (lower limit failure). The
warning displays the station number (2) which was on at the time
of the lower limit violation, the Master Valve (MV1) and/or the
Pump, as well as the GPM reading (12) as measured by the flow
meter. Upon detection, the controller automatically terminates
irrigation on the station and advances to the next station in the
program. Condemned stations will not irrigate again until the
warning has been cleared.
Action:
Step 1 Alarm generation may be caused by:
a. Mis-adjusted valve
b. Incorrectly established individual station limits
c. Large variations in static water pressure
d. Improper regulation
e. Line impediments
Step 2 If station limits are suspected, manually turn each
station on and observe the nominal GPM readings.
To isolate the suspect station, refer to the Manual
Test procedure, (8-2).
Step 3 Compare the GPM reading with the limit setting to
insure that adequate margin exits (typical: 50%
below nominal).
WARNING = FLOW LOW LIMIT
06/20/96 10:45AM
STA=2, MV1 GPM=12 |¾||½|