Rain Master Irrigation Systems DX2 User Manual
Chapter 10: Troubleshooting Page 221
Verify cable connections (with AC power off)
from “PCDX2=MV” board to main circuit board.
Cable p/n 417-2100
Is there
12 – 14 VAC
present?
No
No
Yes
6
8
9
7
A
Replace Fuse F1
(1 Amp)
**This method checks the fuse without removing fuse.
A good fuse will not indicate a voltage since each end
is the same electrical point and would read virtually
zero 0 volts.
Yes
Consult
Factory
Ref. (2-13)
Measure AC voltage across each end of Fuse
F1
Is there
12 – 14 VAC
present?
**
Consult Factory
Vedere la pagina 60