Rain Master Irrigation Systems DX2 User Manual
Chapter 10: Troubleshooting Page 195
022 - FM - Multiple Flow Sensor 2 Assignment
Figure 163: Warning 022-FM Multiple Flow Meter 2 Assign
This warning appears at the submaster whenever the Flow Max
feature has been incorrectly setup by the user. Using Flow Max,
it is possible to assign a device (in this case Flow Sensor 2) to
any of the Flow Max participants. If the flow sensor is assigned
to more than one satellite, this warning will appear at the
submaster. Devices must be installed at one physical location
(satellite) only.
Action:
Step 1 Review the Flow Max device connection list at the
submaster via the F4=REVIEW ALL selection.
Look for two or more occurrences of Flow Sensor 2
throughout the Flow Max participants.
Step 2 Note the incorrect assignment and remove it from
the location(s) which are in error.
Example:
Assume a flow sensor physical connection at the
submaster (address 01-00) and an inadvertent
assignment of Flow Sensor 2 at participant
address 01-03.
To remove the incorrect assignment, go to the
satellite address 01-03 (fourth controller on the
hardwire link) and delete the entry using the
Flow Max setup function.
Step 3 IMPORTANT:
Upon resolution of problem, CLEAR all warnings at
the satellites.
WARNING = MULTIPLE FM 2 06/14/96 11:45AM